Fire Detection
Despite careful attention to the location, design,
construction, and operation of the AIS facility, there is
still the possibility of a fire. Experience shows
repeatedly that prompt detection is a major factor in
limiting fire damage. Typically, a fire goes through
three stages. Some event, such as a failure of electrical
insulation, causes ignition. An electrical fire will often
smolder for a long period of time. When an open flame
develops, the fire spreads through direct flame contact,
progressing relatively slowly, with a rise in the
temperature of the surrounding air. The duration of this
stage is dependent on the combustibility of the materials
at and near the point of ignition. Finally, the
temperature reaches the point at which adjacent
combustible materials give off flammable gases. At
this point, the fire spreads rapidly and ignition of nearby
materials will result from heat radiation as well as direct
flame contact. Because of the high temperatures and
volumes of smoke and toxic gases associated with this
third stage, fire fighting becomes increasingly difficult
and often prevents people from remaining at the fire
site.
Given the objective to discover and deal with a fire
before it reaches the third stage, one can see the
limitation of fire detection that depends on detecting a
rise in air temperature. For this reason, the areas in
which electronic equipment is installed should be
equipped with products-of-combustion (smoke)
detectors. Such detectors use electronic circuitry to
detect the presence of abnormal constituents in the air
that are usually associated with combustion.
In designing an effective fire detection system,
consider the following points:
Location and spacing of detectors. The
location and spacing of detectors should take
into consideration the direction and velocity of
air flow, the presence of areas with stagnant air,
and the location of equipment and other potential
fire sites. Note that detectors may be required
under the raised floor, above the hung ceiling,
and in air-conditioning ducts as well as at the
ceiling. It may also be wise to put detectors in
electric and telephone equipment closets and
cable tunnels.
Control panel design. The design of the
detection control panel should make it easy to
identify the detector that has alarmed. This
implies that the detectors in definable areas (for
example, the tape vault, the east end of the
4-20
computer room, and administrative offices)
should be displayed as a group on the control
panel. In other words, when an alarm sounds,
inspection of the control panel should indicate
which area or zone caused the alarm. Generally,
and preferably, each detector includes a pilot
light that lights when the detector is in the alarm
state. In some cases there should be a separate
indicator light at the control panel for each
detector. It is also important to see that the alarm
system itself is secure. Its design should cause a
trouble alarm to sound if any portion of it fails,
or if there is a power failure. Take steps to assure
the system cannot be deactivated readily, either
maliciously or accidentally.
Personnel response. Meaningful human
response to the detection and alarm systems is
necessary if they are to be of any value. This
means the fire detection system should be
designed to assure that someone will always be
alerted to the fire. Typically, the computer room
staff is expected to respond to an alarm from the
AIS facility alarm system. A remote alarm
should also be located at another point in the
building that is occupied at all times, such as the
lobby guard post, security center, or building
engineers station. This provides a backup
response when the computer area is not
occupied. If there is any possibility the remote
alarm point will not be occupied at all times, a
third alarm point should be located offsite,
usually at the nearest fire station or the
commands fire department for the facility.
Maintenance. Proper maintenance is essential
to the fire detection system. The nature of smoke
detectors is such that nuisance alarms may be
caused by dust in the air or other factors.
Because of this, there is a tendency to reduce
sensitivity of the detectors to eliminate nuisance
alarms, with the result that detection of an actual
fire may be delayed. To ensure proper operation,
see that qualified personnel (a vendor
representative, building engineer, or Public
Works Center personnel) verify correct
operation at the time of installation, and at least
once each year thereafter. Furthermore, each
fault condition should be corrected immediately.
Unfortunately, a common tendency is to turn off
the fire detection system or silence the alarm
bell, creating the danger that there will be no
response if a fire should occur.